10VT1產(chǎn)品概述
The T Series RFI filters provide superior common-mode and premium differential-mode attenuation for current ratings up to 20 amps in package sizes smaller than comparable EP Series filters. These filters are a size and cost-effective choice for very noisy equipment that must meet the emission limits of FCC Parts 15 and 18 or EN55022, A-level (and in some cases B-level). This performance is accomplished with circuits that still meet the very low leakage current requirements of VDE portable equipment and (120 Volt) UL544 non-patient medical equipment. Maximum Leakage Current (Line-to-Ground): ET Models: (3 A, 6 A, 10 A, 15 A) 0.30 mA @ 120 VAC, 60 Hz; (3 A, 6 A, 10 A, 15 A) 0.50 mA @ 250 VAC, 50 Hz; VT Models: (10 A) 0.75 (15 A) 1.2 mA @ 120 VAC, 60 Hz; (10 A) 1.25 (15 A) 2.0 mA @ 250 VAC, 50 Hz. Hipot Rating (1 minute): Line-to-Ground — 2250 VDC; Line-to-Line — 1450 VDC. Operating Frequency: 50/60 Hz. Maximum Rated Voltage: 250 VAC.